Permit Number: T20CM04582
Parcel: 118038210

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM04582
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2021 STEVE SHIELDS ZONING REVIEW Reqs Change FROM: Steve Shields
Site Section Manager

PROJECT:
T20CM04582
2550 W Sunstar Pl
Addition

TRANSMITTAL: January 5, 2021
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

Perimeter yard setbacks are based on a measurement from design grade to the highest point of the exterior wall.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). Based on a wall height of 19’-4” the required perimeter yard setback is 12’-11”, proposed perimeter yard setback is not provided but it does not appear that the setback is met. Provide the proposed setback so that complete comments can be provided for the Design Development Option.
12/16/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed