Permit Review Detail
Review Status: Active
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T20CM04561
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/21/2020 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Section Manager PROJECT: T20CM04561 5671 E Calle Silvosa Bedroom and Garage Addition Residential (1st Review) TRANSMITTAL DATE: July 21, 2020 The room addition plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10. 1. There is an "EXISTING RAMADA" shown just north of the proposed garage. This ramada does not show on the most current aerial photo and there are no permits in our system. Provide approve documents for the ramada or it will need to be part of this permit. 2. Provide a signed application with your next submittal. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 07/21/2020 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 07/21/2020 | SSHIELD1 | NPPO | REVIEW | Passed | |
| 07/21/2020 | PIMA COUNTY | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | PROVIDE SHEET #4 ROOF FRAMING PLAN. PROVIDE A PLUMBING PLAN FOR THE NEW BATHROOM SHOWN ON SHEET #3 FLOOR PLAN. PLANS FOR A CARPORT REQUIRE FILE NAMES AND SHEET NUMBERS. EACH SET OF PLANS SHOULD BE CONTAINED WITHIN A SINGLE PDF FILE. |