Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM04537
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/26/2020 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | Provide a complete plan set for review. Include a completed Site Plan; Roof Framing Plan with dimensions, post locations, beam and rafter sizes; and a Section Detail noting footer size, rebar and all fastening points, sheathing size and type of covering. Identify all structural components for wind loading and 2018 IRC compliance as displayed at the web-site: https://www.tucsonaz.gov/pdsd/building-codes K E Van Karsen 520 837-4912 |
| 09/02/2020 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Section Manager PROJECT: T20CM04537 530 W. Holladay Dr Porch Addition Residential (2nd Review) TRANSMITTAL DATE: September 2, 2020 The plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards .9.7.B.6, .9, & .10 1. Provide a plot plan that meets the following requirements; https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf The drawing plan shall be submitted as a single multi-page PDF. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |