Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM04495
Parcel: 138210440

Address:
140 W TETON ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM04495
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2020 LOREN MAKUS ENGINEERING REVIEW Passed
07/17/2020 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: T20CM04495
140 W Teton St
Enclose Carport to Room and add Porch
Residential (1st Review)

TRANSMITTAL DATE: July 17, 2020

The room addition plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

1. Provide a lot coverage calculation needs to be updated to include the shed square footage.

2. Provide a legal description on the plan

3. Provide the zoning for all adjacent parcels including the parcel south of Teton.

4. Provide a dimension from the centerline of Teton to the curb and from the curb to the south property line. The distance from centerline to the face of curb should be 14' and from the face of curb to the property line is 11'

5. Show the proposed porch on the plot plan and indicate that the carport is to be enclosed to a room.

6. Remove the street sidewalk shown on the plot plan as it does not exist.

7. The plan set shall be submitted as a single multi-page pdf not individual sheet.

8. Provide a signed application with you next submittal. Also, the application Description of Work states Carport Addition & Garage. There is not garage shown on the plans and the porch is labeled as a carport, correct the plans.

Residential plot plan requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
07/17/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM04495
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.

Consolidate pages of construction plans into a single .PDF file as prescribed at the PDSD web site. https://www.tucsonaz.gov/pdsd/online-permits

SITE PLAN:

1. Indicate the location of the existing and proposed buildings, utility meters and gas, water, electric and sewer or septic lines from property line to building, R106.1.1.

STRUCTURAL PLANS:

1. Provide complete roof and floor framing plans. Show rafter size and spacing, R301.1.
2. Show a composite beam with staggered fasteners when assembling with rafters, R301.1.

SECTIONS - DETAILS:

1. Update cross-section detail on sheet A-1.7. Show wood framed walls with minimum ½” x 10” anchor bolt spacing and treated sill plates, R602.10.8 & R403.1.6.
2. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.

MECHANICAL PLANS:

1. Provide heating facilities in all habitable rooms, R303.9.

ELECTRICAL PLANS:

1. Provide an Electrical service utility plan coordinated with Tucson Electric Power. TEP usually requires meters not to be relocated under roof structures, TEP SR-405.10.L. Also, overhead service conductors require an 8’ clearance above a low sloped roof, E3604.2.1.
2. Show receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet, E3901.2.
3. Protection of all interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors requires combination type arc-fault circuit interrupters, E3902.16.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
07/17/2020 SSHIELD1 NPPO REVIEW Passed