Permit Number: T20CM04477
Parcel: 117190750

Address:
522 W 17TH ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM04477
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2020 PIMA COUNTY BUILDING-RESIDENTIAL REVIEW Reqs Change A DWELLING WITH WINDOW OPENINGS MAY NOT BE PLACED WITHIN THE FIRE SEPARATION DISTANCE OF 3 FEET TO PROPERTY LINE. REQUIRES REDESIGN WITH APPROPRIATE FIRE RATINGS BEFORE REVIEW. R302.1.
08/03/2020 ALEXANDRA HINES ZONING REVIEW Reqs Change FROM: Alexandra Hines, AICP – Lead Planenr

PROJECT: T20CM04477 – 522 W 17th St – Renovate and Add to Existing Residence

COMMENTS: the following comments are relative to an application for Historic Review (UDC 5.8.8).

This site is located in the HO-3 zone (UDC 4.7.15).

The proposed setback is 2’. The required setback from east property line is 8’ 6” based on 12’ 8” height (Table 6.3-3.A).

The proposed setback is 6’ 11”. The required setback from west property line is 8’6” based on 12’8” height (Table 6.3-3.A).

HPZ process has to granted setback modification. If not granted in Approval letter, apply for DDO process.

Separate application approval required prior to zoning approval.
08/03/2020 AHINES2 ENGINEERING REVIEW Passed
08/03/2020 AHINES2 NPPO REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/27/2020 JGARCIA1 APPROVAL SHELF Completed
08/27/2020 JGARCIA1 OUT TO CUSTOMER Completed
08/27/2020 JGARCIA1 REJECT SHELF Completed