Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM04465
Parcel: 136244080

Address:
6928 E NELSON DR

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM04465
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2020 ANDREW CONNOR NPPO REVIEW Passed
07/16/2020 LOREN MAKUS ENGINEERING REVIEW Passed
07/16/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM04465
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

Sample plans are available on request. PDSD-Residential@tucsonaz.gov

SITE PLAN:

Provide a site plan showing all buildings, R106.1.1. Show setbacks to property line.

FLOOR PLAN:

Provide a floor plan showing each room with labeled function. Scale ¼” = 1’. Show proposed window size. Also, show adjacent existing rooms with egress from bedrooms.

SECTIONS - DETAILS:

Provide structural details showing code compliant materials and fasteners. Show complete foundation with dimensions, anchor bolts and rebar.

MECHANICAL PLANS:

Provide equipment details showing code compliant components and sizes.

ELECTRICAL PLANS:

Provide wiring details showing code compliant devices and sizes. Show circuit size with receptacles at all walls and lighting control at each doorway.

INTERNATIONAL ENERGY CONSERVATION CODE:

Provide insulation details showing code compliant materials and sizes, N1101. Show insulation rating.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
07/17/2020 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: T20CM04465
6928 E Nelson Dr
Room Expansion
Residential (1st Review)

TRANSMITTAL DATE: July 17, 2020

The room addition plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

1. Provide a plot plan than meets the requirement below.

Residential plot plan requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956