Permit Number: T20CM04416
Parcel: 141113810

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM04416
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/11/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. No compliance with comment #2 from the previous plan review.
2. It was noted that the new service equipment is feeding various equipment. Is this new or existing equipment. Please identify as such.. If new, provide a complete electrical floor plan showing the locations of the equipment and panels.
3. The other drawing does not correlate with the sealed drawing. Please clarify.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/15/2020 VLEON1 APPROVAL SHELF Completed
10/15/2020 VLEON1 OUT TO CUSTOMER Completed
10/15/2020 VLEON1 REJECT SHELF Completed