Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T20CM04416
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/05/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Please provide a complete line diagram sealed by an Electrical Engineer registered in the State of Arizona. Provide compliance with NEC art 230. Include all conduit, conductor sizes and types, load calculations, fault current ratings. Etc. 2. Provide a site plan showing the electrical equipment locations on the site. 3. Provide complete panel schedules. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/09/2020 | VFLORES1 | APPROVAL SHELF | Completed |
| 09/09/2020 | VFLORES1 | OUT TO CUSTOMER | Completed |
| 09/09/2020 | VFLORES1 | REJECT SHELF | Completed |