Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM04397
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/22/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
07/24/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Ref; Plan Sheet E-1. The receptacles at the bottom right location are off the electrical floorplan. Please correct and resubmit with the outlets located correctly on the plan. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |
07/31/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Spaces in which factory-built recirculating hoods tested in accordance with UL 710B are installed are considered to be kitchens and shall be ventilated per Section 403.3.1.1, IMC 2018. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual cooking appliance (e.g. Turbochef oven, Steam oven, microwave oven, etc.). Reference: Section 507.1, exception 2, IMC 2018 |
07/31/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Appliances (e.g. steam oven, condensing hood, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.14.1, IPC 2018 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2018. |
07/31/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
08/06/2020 | NICHOLAS ROSS | ZONING | REVIEW | Approved | |
08/06/2020 | NROSS1 | ENGINEERING | REVIEW | Passed | |
08/21/2020 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/21/2020 | JGARCIA1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/21/2020 | JGARCIA1 | APPROVAL SHELF | Completed |
08/21/2020 | JGARCIA1 | OUT TO CUSTOMER | Completed |
08/21/2020 | JGARCIA1 | REJECT SHELF | Completed |