Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T20CM04395
Parcel: 133369540

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM04395
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved