Permit Number: T20CM04394
Parcel: 11205283G

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM04394
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2020 JPEELDA1 FIRE REVIEW Approved
07/22/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the gas pipe size for the two hot plates. Based on the demand and developed pipe length for the appliances, each unit requires a 1" branch and the pipe serving both appliances should to be 1-1/4" (360 CFH @ 90-feet). Reference: Sections 402.1 and 402.3, IFGC 2018.
07/22/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show the size of the Type I grease hood, verify that the canopy of the hood extends beyond the cooking appliances by at least 6-inches, and the hood is listed for the type of appliances located under it. Reference: Sections 507.4 and 507.5, IMC 2018.
07/22/2020 ROBERT SHERRY WATER REVIEW Completed
07/24/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide complete electrical power and lighting plans, sealed by a registrant registered in the state of Arizona. See City of Tucson Electrical Commercial Plan Submittal Requirements can be downloaded at www.tucsonaz.gov/pdsd; Permit Review; Commercial Permits; Commercial Plan Review. Include branch circuit designations, panel schedules, Indicate clearly all light fixture symbols and their associated inverter.
Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code.
Ref; 2018 IBC sec. 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code
08/06/2020 NROSS1 ENGINEERING REVIEW Passed
08/06/2020 NICHOLAS ROSS ZONING REVIEW Approved
08/20/2020 JGARCIA1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/21/2020 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/21/2020 JGARCIA1 APPROVAL SHELF Completed
08/21/2020 JGARCIA1 OUT TO CUSTOMER Completed
08/21/2020 JGARCIA1 REJECT SHELF Completed