Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM04394
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/14/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 07/22/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Revise the gas pipe size for the two hot plates. Based on the demand and developed pipe length for the appliances, each unit requires a 1" branch and the pipe serving both appliances should to be 1-1/4" (360 CFH @ 90-feet). Reference: Sections 402.1 and 402.3, IFGC 2018. |
| 07/22/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Show the size of the Type I grease hood, verify that the canopy of the hood extends beyond the cooking appliances by at least 6-inches, and the hood is listed for the type of appliances located under it. Reference: Sections 507.4 and 507.5, IMC 2018. |
| 07/22/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/24/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide complete electrical power and lighting plans, sealed by a registrant registered in the state of Arizona. See City of Tucson Electrical Commercial Plan Submittal Requirements can be downloaded at www.tucsonaz.gov/pdsd; Permit Review; Commercial Permits; Commercial Plan Review. Include branch circuit designations, panel schedules, Indicate clearly all light fixture symbols and their associated inverter. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code. Ref; 2018 IBC sec. 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code |
| 08/06/2020 | NROSS1 | ENGINEERING | REVIEW | Passed | |
| 08/06/2020 | NICHOLAS ROSS | ZONING | REVIEW | Approved | |
| 08/20/2020 | JGARCIA1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/21/2020 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/21/2020 | JGARCIA1 | APPROVAL SHELF | Completed |
| 08/21/2020 | JGARCIA1 | OUT TO CUSTOMER | Completed |
| 08/21/2020 | JGARCIA1 | REJECT SHELF | Completed |