Permit Number: T20CM04299
Parcel: 125050420

Address:
720 N PLUMER AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM04299
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2020 STEVE SHIELDS ZONING REVIEW Approved
07/09/2020 SSHIELD1 ENGINEERING REVIEW Passed
07/09/2020 SSHIELD1 NPPO REVIEW Passed
07/09/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM04299
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SECTIONS - DETAILS:

1. Specify the minimum thickness of structural siding, R602.10.3.4, and a #15 water-resistive barrier over studs/sheathing of all exterior walls, R703.2. OSB may be 3/8” thickness as a structural sheathing.
2. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-30 for areas under 500SF.

PLUMBING PLANS:

1. Show plumbing alterations, 2018 IRC.

MECHANICAL PLANS:

1. Show mechanical system alterations, 2018 IRC.

ELECTRICAL PLANS:

1. Show electrical alterations, 2018 IRC.
2. Interior alterations require the installation of smoke alarms at existing bedrooms, R314.2.1. Provide notation if the smoke alarms are existing or proposed.
3. Show receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet in altered areas, E3901.2.
4. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3. GFCI protected, E3902.6.
5. Show a receptacle outlet within 3’ of each lavatory basin in each bathroom, E3901.6. Show Bathroom receptacles on a separate 20 AMP circuit (dedicated) with outlets at no other location, E3703.4 and E3901.6.
6. Show one 20 AMP branch circuit for the dishwasher/disposal; this circuit may not serve other locations, E3703.8 City of Tucson Amended.
7. Show protection of new and extended interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.16 & E3902.17.
8. Provide notation requiring tamper resistant receptacles for 125 volt, 15A and 20A receptacles, R4002.14.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review