Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM04059
Parcel: 10604198B

Address:
405 E NAVAJO RD

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T20CM04059
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet C1; Cover Sheet: The title block on this sheet indicates 'D1 Demolition Plan'. Please revise.
2. Sheet A1; First and Second Floor Plans: Interior elevations A/A1, B/A1, C/A1, and D/A1 are not included on this sheet. Please provide those elevations.
3. Previous Comment 9; Sheet A3; North Elevation: The Second Floor Plan on Sheet A1 does not indicate a new window at the east end (Unit B bedroom) as shown on the North Elevation. Please verify.
4. Sheet A3; West Elevation: This Elevation indicates only two second floor windows, while the plan on Sheet A1 indicates three windows. Please verify.
5. Sheet A4; Wall Sections: Please indicate Wall Section A and B on those sections.
6. General: Please provide written responses to all review comments.
04/08/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The energy code compliance calculations for the alteration to the building envelope were not included in the resubmittal. [Initial comment: Demonstrate energy code compliance for the alteration to the building envelope using calculations based on the current code. Reference: Sections R503.1.1 through R403.2, International Energy Conservation Code 2018.]
2. The energy code compliance calculations for the addition to the building envelope were not included in the resubmittal. [Initial comment: Provide energy code compliance calculations for the addition to the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the addition to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections R503.1.1 through R403.2, International Energy Conservation Code 2018]
3. The heating and cooling load calculations were not included in the resubmittal. [Initial comment: Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section R403, IECC 2018.]
4. The heat pump units are still shown on multiple floors; only the ducts from the units should be shown on the 1st and 2nd floors. Ducts in shafts will require fire dampers (Section 607.6, IMC 2018). [Initial comment: Clarify the mechanical plan. Why are 5 package heat pumps shown for the three dwelling units? Reference: Section 107.2.1, IBC 2018.If the three heat pumps are located on the roof, why are they also shown on the 1st floor and the 2nd floor?]
5. The duct sizes, routes, and termination points for the exhaust fans were not shown. [Initial comment: Show the locations, duct sizes, and termination points for the exhaust fans. Reference: Section 107.2.1, IBC 2018.]
6. An exhaust vent for a clothes dryer is not an exhaust fan, show the size, route and termination for the dryer exhaust vents. [Initial comment: Show the location, termination, and size of the exhaust vents for the three clothes dryers. Reference: Sections 504.1 and 504.4, IMC 2018.]
04/08/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Provide for Arc Fault branch circuit interrupters as required per NEC 210.12.

Verify that a minimum or 2- 20 amp branch circuits are assigned for countertop receptacles for the kitchen countertops as required per NEC 210.52A(4).

Provide a complete electrical line diagram of the electrical service and downstream equipment. Include total building load calculations. Verify AIC ratings of the New Panels. 27800K is not a NEMA standard rating for a load center.

Verify the light source color temperature for the exterior luminaires does not exceed 3500K per OLC section 402.1.

Provide for Tamper Resistant Receptacles to be utilized as required per NEC art, 406.12.

Provide for a switched lighting outlet in the Air Handler closet if applicable, per NEC 210.70A(3).

Show the location and branch circuit assigned for all Smoke Detectors. NEC 408.4, 2018 IBC.

Provide complete compliance with the 2018 IECC for the lighting.



Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code (OLC).
04/08/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify the size of the water service to the building. It is currently dimensioned as ¾”. [Initial comment: Show how the domestic water enters the building. Reference: Section 107.2.1, IBC 2018.]
2. The waste & vent riser diagram is incomplete. Show the pipe dimensions on the diagram; very few dimensions are shown on the plans. [Initial comment: Provide a waste & vent riser diagram; coordinate the 1st floor waste piping with the 2nd floor waste piping. Reference: Section 107.2.1, IBC 2018.]
3. The detail is incomplete; show the excess pressure relief, vacuum relief or other anti-siphon device and valves. [Initial comment: Provide a detail of the water heater installation for the 2nd floor and 2-story units, including the excess pressure relief, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503.1, 504, 606.1, IPC 2018.]
4. Provide a safety pan for the water heater. Show the point of termination for the T&P relief. [Initial comment: Provide a detail of the water heater installation for the 1st floor unit, including the excess pressure relief, recirculation system, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503.1, 504, 606.1, and 607.2, IPC 2018.]
5. The full-open valves for the water supply to each dwelling unit are to be accessible. Note that the cold water for unit B on the 2nd floor is provided by unit C. [Initial comment: Provide a full-open valve for the water supply entrance to each dwelling unit unless each fixture is equipped with stop valves. Reference: Section 606.1(6), IPC 2018.
6. Label the hot water recirculation pipe as “HWR”, not “HW”. The hot water return pipe is to connect to the cold water inlet to the water heater on the plumbing plans just as shown on the detail (Section 607.2.2, IPC 2018). Show the shut off and check valves associated with the recirculation system on the detail. [Initial comment: The developed length of the hot water supply piping for the 1st floor unit appears to be greater than fifty feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2018 and C404.5, IECC 2018.]
7. Drafting comment: the old plumbing fixture schedule is now located over the bathrooms of unit A.
04/12/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: Development Services Department Zoning Review

PROJECT:
T20CM04059
405 e Navajo Rd.
Addition to 3 Unit Multi-family

TRANSMITTAL: April 12, 2021
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-3 zone (UDC 4.7.12). Multi-family residential is a permitted use in this zone (Table 4.8-2). See Use Specific Standards 4.9.7.B.6.

Perimeter yard setbacks are based on a measurement from design grade to the highest point of the exterior wall, see UDC Article 6.4.5.B and Figure 6.4.5-A. As the height shown on the elevations is to finished floor, 6” has been added to the height shown on the elevations or 20’-6” from design grade.

The following comment was not addressed.

1. The minimum setback is the greater of ten (10) feet, or three-fourth (3/4) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). Based on a wall height of 20’-6” the required perimeter yard setback from the proposed 2nd floor addition is 15’-5”. Proposed setback to the east property line is 13’-9” and to the west property line is 13’-6”, Design Development Option (DDO) will need to be submitted and approved. The provided elevations in the building set do not match the heights provided on the development package DP20-0044.

If you have any questions about this transmittal, please contact Elisa Hamblin at ElisaHamblin@tucsonaz.gov.