Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Please provide a site plan with the existing building located on that plan. In addition, provide a brief project narrative on that sheet, indicating the scope of the work.
2. General: Please provide a project valuation (labor + materials).
08/05/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide legible documents (PDF)
2. Verify that the equipment sizing complies with Section C403.3.1, IECC 2018 (i.e. do not oversize the AC unit).
08/05/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Passed