Permit Number: T20CM04056
Parcel: 111083580

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM04056
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Initial comment: Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.]
2. Comment not addressed. [Initial comment: Provide plans that show the extent of work to be performed and show that the work will conform to all relevant laws, ordinances, and codes. Reference: Section 107.2.1, IBC 2018.]
3. Comment not addressed. [Initial comment: Provide underground facility tracer wires per ARS 40-360.22.]
4. Comment not addressed. [Initial comment: Provide a full-open valve for the water service at the building entrance. Reference: Section 606.1(2), IPC 2018.]
5. Comment not addressed. [Initial comment: Show how the service hot water distribution system (note that the system is not a heating hot water system) complies with the requirements of Sections 607.2 and 607.2.1, IPC 2018 and Section R403.5.1, IECC 2018.]
6. Comment not addressed. [Initial comment: Show how the service hot water distribution piping will be insulated. Reference: Section R403.5.3, IECC 2018.]