Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T20CM04056
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/16/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Provide plans that show the extent of work to be performed and show that the work will conform to all relevant laws, ordinances, and codes. Reference: Section 107.2.1, IBC 2018. 3. Provide underground facility tracer wires per ARS 40-360.22. 4. Provide a full-open valve for the water service at the building entrance. Reference: Section 606.1(2), IPC 2018. 5. Show how the service hot water distribution system (note that the system is not a heating hot water system) complies with the requirements of Sections 607.2 and 607.2.1, IPC 2018 and Section R403.5.1, IECC 2018. 6. Show how the service hot water distribution piping will be insulated. Reference: Section R403.5.3, IECC 2018. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/17/2020 | KROBLES1 | OUT TO CUSTOMER | Completed |