Review Details: RESUBMITTAL
Permit Number - T20CM04049
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/28/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/02/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | There were no changes made to the project drawings A-1, A-2, or A-3 in response to the first review comments. 1. Sheets A-1, A-2, A-3, and A-4: Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that in addition to signing the seal, the registrant shall include the date the document was sealed. 2. Sheet A-1; Site Plan: The exterior wall descriptions reference the 2000 IBC Table 719.1(2), Items 1-1.2 and 3-1.1. for fire resistance ratings. Please revise the references and item numbers to the 2018 IBC. 3. Sheet A-1; Site Plan: Please indicate on this drawing the interior separation wall is a two hour fire barrier per the IBC Table 508.4. 4. Sheet A-2; Project Data (Allowable Areas): Please revise the allowable areas using the IBC Table 506.2 and Section 508.4 for separated occupancies. 5. Sheet A-2; Codes: Please add the 2009 ICC/ANSI A117.1 accessibility code to this list. 6. Sheet A-2; Project Data: Please indicate the allowable building height in feet (Table 504.3) and in stories (Table 504.4) on this sheet. 7. Sheet A-2: Please provide plumbing calculations on this sheet for the required water closets (male and female), lavatories (male and female), drinking fountains (high/low or single point of use), and servise sinks. 8. Sheet A-2; Floor Plan: The floor plan indicates a one hour rated corridor for exiting. However, the west side of this corridor (along the Conference Room and Women's Toilet) is required to be enclosed with a one hour rated fire partition. Please provide. 9. Sheet A-3; Toilet Clearances (Side Wall): Please locate the vertical grab bar from the back wall per the ICC/ANSI Figure 604.5.1. 10. Sheet A-3; Toilet Clearances (Side Wall): The horizontal grab bar indicates a 12" minimum dimension from the back wall to the grab bar. Please revise that to 12" maximum per the ICC/ANSI Figure 604.5.1. 11. Sheet A-3; Toilet Clearances (Back Wall): Please revise the location of the horizontal grab bar per the ICC/ANSI Figure 604.5.2. 12. Sheet A-3; North Men's and North Women's Elevations: Please indicate the vertical grab bar on these elevations. 13. General: An application is required for this project. Please provide. 14. General: Please provide written responses to all review comments. |
| 09/16/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The outside air schedule still references ASHRAE 62-1989 and the UBC. The City of Tucson did not adopt ASHRAE Standard 62.1 for ventilation calculations and the 2018 IMC only references the ASHRAE Standard for the purpose of calculating the system ventilation efficiency (Ev). Provide calculations to show that the ventilation system is sized in accordance with Section 403.3, IMC 2018; for HVAC systems serving multiple zones (e.g. AC-5 and AC-6), see Section 403.3.1.1.2.3, IMC 2018. [Initial comment: The ventilation calculations ("Fresh Air Schedule") are based on the UBC and ASHRAE 62-1989. Provide calculations based on the current code to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018.] 2. Comment not resolved; the calculations are based on weather conditions in Phoenix and they don't appear to include the building occupants or the mechanical ventilation. Provide a summary of the calculations showing the total and sensible cooling loads being handled by each AC unit. [Initial comment: Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.] |
| 09/16/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not resolved; seals are still not dated. [Initial comment: Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that in addition to signing the seal, the registrant shall include the date the document was sealed.] 2. Per the manufacturer of the specified temperature mixing valve, TV-1, it is not listed to ASSE Standard 1070 and, "…[it] cannot be used for tempering water temperature at fixtures." In addition, tempered water is defined as being between 89- and 110-degrees Fahrenheit. Reference: Sections 202, 303.2 and 419.5, IPC 2018 [Initial comment: Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. (Why does the plumbing fixture schedule show no water connections for lavatory L-1?) Reference: Sections 416.5 and 607.1.2, IPC 2018.] 3. Section C404.5 requires a maximum distance of 2-feet from the hot water source to the lavatory stop valve when using ½" branch pipe. [Initial comment: Verify that the distance from the hot water source (i.e. the recirculating hot water loop) to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.] |
| 09/16/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 10/02/2020 | MALLORY RESS | ZONING | REVIEW | Reqs Change | FROM: Mallory Ress PDSD Zoning Review Section PROJECT: T20CM049049 Luz Y Vida Church – TI (2nd Review) 225 W AJO WY TRANSMITTAL DATE: 10/02/20 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 01. COMMENT: The provided parking plan shows that the parking requirements found under 7.4.4 are not met for the religious use, applicant may utilize the 3.3.3.H waiver, to be granted zoning compliance for parking standards. Link provided below: https://www.tucsonaz.gov/files/pdsd/forms/C_of_O_Releif_Affidavit.pdf If you have any questions about this transmittal, Contact Mallory Ress at Mallory.ress@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Completed and Signed 3.3.3.H waiver |