Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM04049
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/10/2020 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Tucson Water records indicate that a 5/8" water meter serves this building. Tucson Water limits a 5/8" meter to a maximum demand of 20 GPM. Determine the water demand for the building and revise the meter size as needed. 2. Provide the size and location of the reduced pressure backflow prevention assembly serving this building. Reference: Section 107.2.1, IBC 2018. 3. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf |
| 07/13/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that in addition to signing the seal, the registrant shall include the date the document was sealed. 2. Revise detail 8/MP-2 to show the water heater installed correctly and, in a manner consistent with the manufacturer's instructions (i.e. the cold water inlet is at the top of the unit). (Note that the specified water heater was discontinued in 2015. Reference: Section 303.2, IPC 2018. 3. Provide the number of drinking fountains that complies with the requirements of Sections 1109.5, 2902.1 and 2902.5, IBC 2018 and Section 410.3, IPC 2018. 4. Provide metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 5. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. (Why does the plumbing fixture schedule show no water connections for lavatory L-1?) Reference: Sections 416.5 and 607.1.2, IPC 2018. 6. Verify that the distance from the hot water source (i.e. the recirculating hot water loop) to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018. 7. Verify the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson. |
| 07/13/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 07/13/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The ventilation calculations ("Fresh Air Schedule") are based on the UBC and ASHRAE 62-1989. Provide calculations based on the current code to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018. 2. Update the natural ventilation calculations for the storage room using the current code. Reference: Sections 402.1and 402.2, IMC 2018. 3. Revise the sequence of operation for the restroom exhaust fan, EF-1, so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2018. 4. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018. 5. Show that the proposed AC units meet the requirements of Sections C403.3, C403.4, and C403.5 (e.g. provide the mechanical compliance certification from COMcheck). Reference: Section C501.4, International Energy Conservation Code 2018. 6. Show that each rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and automatic start-up control (i.e. the thermostat is capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy) and, if the thermostat does not require manual changeover from the heating and cooling modes, it restricts set point overlap. Reference: Section C403.4.2 through C403.4.2.3, IECC 2018. |
| 07/15/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide compliance with the 2018 IECC for the lighting. 2. Provide for Tamper Resistant Receptacles where applicable per NEC 406.12. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |
| 07/24/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 08/03/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/03/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheets A-1, A-2, A-3, and A-4: Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that in addition to signing the seal, the registrant shall include the date the document was sealed. 2. Sheet A-1; Site Plan: The exterior wall descriptions reference the 2000 IBC Table 719.1(2), Items 1-1.2 and 3-1.1. for fire resistance ratings. Please revise the references and item numbers to the 2018 IBC. 3. Sheet A-1; Site Plan: Please indicate on this drawing the interior separation wall is a two hour fire barrier per the IBC Table 508.4. 4. Sheet A-2; Project Data (Allowable Areas): Please revise the allowable areas using the IBC Table 506.2 and Section 508.4 for separated occupancies. 5. Sheet A-2; Codes: Please add the 2009 ICC/ANSI A117.1 accessibility code to this list. 6. Sheet A-2; Project Data: Please indicate the allowable building height in feet (Table 504.3) and in stories (Table 504.4) on this sheet. 7. Sheet A-2: Please provide plumbing calculations on this sheet for the required water closets (male and female), lavatories (male and female), drinking fountains (high/low or single point of use), and servise sinks. 8. Sheet A-2; Floor Plan: The floor plan indicates a one hour rated corridor for exiting. However, the west side of this corridor (along the Conference Room and Women's Toilet) is required to be enclosed with a one hour rated fire partition. Please provide. 9. Sheet A-3; Toilet Clearances (Side Wall): Please locate the vertical grab bar from the back wall per the ICC/ANSI Figure 604.5.1. 10. Sheet A-3; Toilet Clearances (Side Wall): The horizontal grab bar indicates a 12" minimum dimension from the back wall to the grab bar. Please revise that to 12" maximum per the ICC/ANSI Figure 604.5.1. 11. Sheet A-3; Toilet Clearances (Back Wall): Please revise the location of the horizontal grab bar per the ICC/ANSI Figure 604.5.2. 12. Sheet A-3; North Men's and North Women's Elevations: Please indicate the vertical grab bar on these elevations. 13. General: An application is required for this project. Please provide. 14. General: Please provide written responses to all review comments. |
| 08/21/2020 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Section Manager PROJECT: Luz Y Vida Church - TI T20CM04049 - 1st Review) TRANSMITTAL DATE: August 21, 2020 1. It does not appear that the vehicle parking requirements are met, see UDC Table 7.4.4-1: MINIMUM NUMBER OF MOTOR VEHICLE SPACES REQUIRED. Provide a vehicle parking space calculation on the plan the provided the number required and provided. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |