Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM04048
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/06/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 07/09/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 07/09/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Demonstrate energy code compliance for the alteration to the building envelope using calculations based on the current code. Reference: Sections C503.1 and C503.3, International Energy Conservation Code 2018. 2. Provide heating and cooling load calculations to justify the heating/cooling capacity of the specified heat pump unit. Reference: Section C403.1.1 and C502.2.3, IECC 2018. 3. What is the design basis for exhaust fan EF-1? Reference: Section 107.2.1, IBC 2018. 4. Sheet M1.1 shows eight unit heaters in the building labeled as UH-1 through UH-8 but the heater schedule on sheet M2.0 appears to have them labeled as H-1 through H-8. Clarify the equipment labels. |
| 07/09/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/14/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please revise the IECC lighting calculations to the current 2018 Code. |
| 07/30/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/30/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet C1.0; Drawing Index: The Drawing Index does not list all of the sheets in this submittal. Please revise. 2. Sheet C1.0 (Scope); Sheet A0.0 (Code Review): The Scope indicates salvage auto part sales, while the Code Review lists only storage and business. Should this also include retail? Please verify. 3. Sheet A0.0; Code Review (Governing Codes): Please indicate the 2009 Edition of the ICC ANSI A117.1. 4. Sheet A0.0 (Code Review); Sheet C1.0 (Site Plan); Sheet C2.0 (Site Plan): The Code Review and Site Plans indicate the building SF as 12,918, but the Occupant Load Calculation in the Code Review indicates only 3655 SF storage + 7966 SF business for a total of 11,621 SF. The IBC Table 1004.5 bases Storage, Business, and Mercantile occupant loads on the gross SF, which means the occupant load should be based on the 12,918 SF. Please verify. 5. Sheet A0.0; Exit Plan: Two of the means of egress exit doors are indicated on Sheet A1.0 as sliding doors. The IBC Section 1010.1.4.3 lists several requirements for horizontal sliding doors that are a component of a means of egress. Please indicate in Keynotes 2 and 6 on Sheet A1.0 that the requirements of that IBC section are met. 6. Sheet A0.0; Exit Plan: Please indicate the exit access travel distances on this sheet using the requirements of the IBC Section 1017.3. In addition, list the allowable distance per the IBC Table 1017.2. 7. Sheet A0.0; Exit Plan Second Floor: Please indicate the exit access travel distances on this sheet. Revise the paths of travel per the IBC Section 1017.3 (unobstructed horizontal and vertical path, not diagonal). 8. Sheet A0.0; Code Review: Please indicate on this sheet the required plumbing fixtures and the fixtures provided, including water closets, lavatories, drinking fountains, and service sink. 9. Sheet A0.0; Code Review: Please indicate on this sheet the allowable SF for this building (per the IBC Section 508.3.2), and the actual SF. 10. Sheet A1.0; Floor Plan: The west portion of this building indicates Parts Counter, Show Room, Display Area, and Used Car Office. These all fall under a Retail Occupancy Classification using the IBC Section 309. Please verify. 11. Sheet A1.0; Floor Plan: The Parts Counter has a Keynote 5 referenced. Please revise that reference. 12. Sheet A1.0; Floor Plan: Please indicate the service sink on this plan. 13. Sheet A4.0: Please list a Window Schedule. 14. General: Please provide a valuation (labor + materials) for this project. 15. General: Please provide written responses to all review comments. |
| 08/10/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 08/17/2020 | MALLORY RESS | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/27/2020 | VLEON1 | APPROVAL SHELF | Completed |
| 08/27/2020 | VLEON1 | OUT TO CUSTOMER | Completed |
| 08/27/2020 | VLEON1 | REJECT SHELF | Completed |