Permit Number: T20CM03952
Parcel: 11615087D

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T20CM03952
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2020 JPEELDA1 FIRE REVIEW Reqs Change Please provide more acurate drawings showing full sizes and obstructions to the roads and existing fire department access. Alos, please reference code and standards being used.
06/25/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/25/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change Please provide more acurate drawings showing full sizes and obstructions to the roads and existing fire department access. Alos, please reference code and standards being used. Provide Code Analysis indicating Occupancy Classification, Construction Type, and SF of each structure.
07/14/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Passed
07/20/2020 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Section Manager

PROJECT: T20CM03952 - Covered Parking Canopies
1707 W St Mary's Rd / O-3 Zoning

TRANSMITTAL DATE: July 20, 2020

DUE DATE: July 23, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Show the required 1'-0" setback from the canopy to the parking area access land, see UDC Article 7.4.6.F.2.a.(1) Access lanes and PAALs must be setback at least one foot from: An open structure, such as a carport or covered pedestrian access path as measured from the closest part of the structure or roof overhang.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
07/21/2020 DTRAMME1 ENGINEERING REVIEW Reqs Change Provide approved DP.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/30/2020 KROBLES1 OUT TO CUSTOMER Completed