Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM03949
Parcel: 133200160

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM03949
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2020 JPEELDA1 FIRE REVIEW Reqs Change 2018 IFC, 907.2.2.1 Ambulatory care facilities. Fire areas containing ambulatory care facilities shall be provided with an electronically supervised automatic smoke detection system installed within the ambulatory care facility and in public use areas outside of tenant spaces, including public corridors and elevator lobbies.

Exception: Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 provided that the occupant notification appliances will activate throughout the notification zones upon sprinkler waterflow.
07/06/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Detail 3/P3.0 shows an "oxygen change-over alarm" for the medical gas manifold. Should that be a "medical air change-over alarm"? In addition, should a "medical air secondary supply in use" alarm be added to the combination master/area alarm panel?
2. Detail 6/P3.0 shows a ZV2 zone valve labeled as "ZV" and noted as a ZV1 zone valve; clarify this.
07/06/2020 ROBERT SHERRY WATER REVIEW Completed
07/06/2020 JOHN VAN WINKLE ENGINEERING REVIEW Passed
07/07/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of AC-2, AC-3, AC-4, and AC-5. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
2. The air balancing data for AC-9 is shown on sheet M2.0 and in the outdoor air calculations on sheet M3.1 but the balancing data for EF-4 is only shown in the outdoor air calculations. Show the balancing data for EF-4 on sheet M2.0. Reference: Section 107.2.1, IBC 2018.
3. Room 223 has 170 CFM of supply, 100 CFM of exhaust, and no return air. Revise the mechanical design as required to avoid using the passage (324) as a return air duct. Reference: Section 601.2, IMC 2018.
07/13/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/20/2020 STEVE SHIELDS ZONING REVIEW Approved
07/29/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet TS1.0; Project Narrative: The narrative indicates a 4460 SF space plus a 923 SF portion of the existing office for a total of 5383 SF. The Code Analysis and the Code Study (both on this sheet) indicate 5008 SF. Please coordinate.
2. Sheet TS1.0; Code Study: Please include a service sink in the required plumbing fixtures per the IBC Table 2902.1, and indicate that sink on the plan.
3. Sheet A0.1; Project Data: The Occupant Load is indicated as 33 on this sheet, while the Code Study on Sheet TS1.0 indicates 34. Please coordinate.
4. Sheet A0.1; Exit Floor Plan: This plan indicates a total occupancy of 33 (6+16+11) for the three exits. Please coordinate with the Code Study on Sheet TS1.0.
5. Sheet A0.1; Exit Floor Plan: The exit path indicated through Room 316 will not work due to the Equipment Layout (Sheet A1.1). Please revise.
6. Sheet A0.2; Detail 11: Please provide elevations for the shower back wall and end wall. Indicate grab bar locations and lengths in addition to the handshower location per the ICC/ANSI Section 608.3.2.
7. Sheet A1.0 (Floor Plan); Sheet A3.0 (Building Section A); Sheet A6.0 (Wall Section 3): Building Section A/A3.0 is cut on the Floor Plan through Room 315. The north partition of that room indicates Type 6FX, which indicates a one hour rated fire barrier. Wall Section 3/A6.0 indicates this partition to be a two hour rated partition. Please coordinate. Does the north partition of Room 315 need to be a rated partition (6XF) except at the shaft enclosure (IBC Section 713)? Please verify.
8. Sheet A1.0; Floor Plan: The interior partitions at the shaft enclosures of Rooms 315 and 316 should be rated per the IBC Section 713. The Partition Types do not include any 4" partitions that require a rating. Please verify.
9. Sheet A1.1; Floor Plan: A portion of the north partition indicates an existing two hour fire partition, while that wall on Sheet A1.0 indicates a one hour rated fire barrier. Please coordinate.
10. Sheet A2.0; Reflected Ceiling Plan: Please verify all exit signs meet the requirements of the IBC Section 1013.1.
11. Sheet A5.0: Please provide enlarged plans for the three new restrooms, indicating accessibility requirements on those plans.
12. Sheet A6.0; Boxed Note: A boxed note indicates to "See Structural Details for All Structural Connections". Please remove that note.
13. General: Please provide written responses to all review comments.
07/29/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/21/2020 VLEON1 APPROVAL SHELF Completed
08/21/2020 VLEON1 OUT TO CUSTOMER Completed
08/21/2020 VLEON1 REJECT SHELF Completed