Permit Number - T20CM03948
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM03948
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.

Consolidate pages of construction plans into a single .PDF file as prescribed at the PDSD web site. https://www.tucsonaz.gov/pdsd/online-permits

ROOF FRAMING PLANS:

1. Consider reducing carport size and providing 3 feet to property line. Provide a complete roof framing plan showing beam and rafter spans.
2. Exterior STRUCTURES with separation distance less than 3-foot to the property line require not less than one-hour fire-resistive construction. Show compliance with R302.1 (City of Tucson Amended) by providing a section detail of materials prescribed in IBC Table 721.1(2), Items 15-1.1 to 16-1.3. Apply fire rated material to the columns.
3. Roof projections extending into the 3-foot fire separation distance require not less than one-hour fire-resistive construction on the underside. Provide notation for compliance with R302.1 (City of Tucson Amended) for the altered roof overhang. The fire protected overhang may not extend closer than 24” from the property line.

STRUCTURAL PLANS:

1. Show a beam size with appropriate load carrying capacity, R301.1.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
08/25/2020 VLEON1 ZONING REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/25/2020 VLEON1 APPROVAL SHELF Completed
08/25/2020 VLEON1 OUT TO CUSTOMER Completed
08/25/2020 VLEON1 REJECT SHELF Completed