Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM03946
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/22/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The specified faucet does not include a means of supplying tempered water using a device that conforms to ASSE 1070. [Initial comment: Provide tempered water for the public restroom lavatory using an approved device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018.] |
| 09/22/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 10/01/2020 | PC_TGUTHEI1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/01/2020 | PC_TGUTHEI1 | REJECT SHELF | Passed |
| 10/01/2020 | PC_TGUTHEI1 | APPROVAL SHELF | Passed |
| 10/01/2020 | PC_TGUTHEI1 | OUT TO CUSTOMER | Completed |