Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T20CM03946
Review Name: WALK THRU - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/25/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. General: Per the IBC Section 107.1, construction documents must be prepared by a registered design professional. Please provide stamped drawings by that individual. 2. General: Drawings must include a site plan, code analysis, description of work, and details/elevations as required. 3. General: Please provide a valuation (labor + materials) for this project. |
| 07/09/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide plans sealed by an Arizona Registrant that are complete and clearly indicate the extent of the proposed work. Reference: Section 107.2.1, IBC 2018.Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. |
| 07/09/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide plans sealed by an Arizona Registrant that are complete and clearly indicate the extent of the proposed work. Reference: Section 107.2.1, IBC 2018.Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. |
| 07/17/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |