Permit Number: T20CM03918
Parcel: 123060760

Address:
2149 E ADAMS ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM03918
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/29/2020 MALLORY RESS ZONING REVIEW Reqs Change FROM: Mallory Ress
Planner

PROJECT:
T20CM03918
2149 E ADAMS ST
RESIDENTIAL ADDITION AND REMODEL

TRANSMITTAL: 6/25/20
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10. A second unit is permitted in the R-1 Zone if the parcel is 10,000sq ft or greater.

The Applicant’s parcel is 15,000sq ft. A second unit is permitted.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A).

Applicant is proposing to modify the western façade of the home in the remodel and addition. The applicant is proposing a 6’4” setback. The wall height is 19’6" measured from natural grade. The required setback is 13’.

DDO is required.
06/29/2020 MRESS1 ENGINEERING REVIEW Passed
06/29/2020 MRESS1 NPPO REVIEW Passed
06/29/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Needs Review
07/07/2020 JVINCEN1 FIRE REVIEW Reqs Change This residence will have a “fire-flow calculation area of 9,286 sq ft”(2018 IFC Appendix B, Section B102 and 105.1) which is greater than 3,600 sq. ft.: therefore this house will require a residential sprinkler system unless the fire flow meets the requirements of Appendix B, 2018 IFC. Additionally, the hydrant must be within 600’ of all parts of the residence. Have a licensed fire sprinkler contractor perform a flow test. Provide notes on plan regarding verification of fire flow and proximity of hydrant or intent to install a fire sprinkler system. If a system will be installed, residential or quick response sprinklers shall be used. The sprinkler system may be connected to the domestic water supply, provided the required design density can be met. Be advised that Tucson Water will not allow a residential sprinkler system to be supplied by a 5/8" meter. A minimum of ¾” meter will be required by Tucson Water. Residential fire sprinkler system shall be installed in accordance with the 2018 IFC and NFPA 13D.