Permit Number: T20CM03737
Parcel: 113074360

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T20CM03737
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2020 STEVE SHIELDS ZONING REVIEW Approved
09/29/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Completed 1. Sheet X1; Code Review Summary: Please revise the ICC/ANSI Edition to 2009.
2. Sheet X1; Code Review Summary: Please revise the Building Classification to R-2 for multi-family housing.
3. Sheet S2.1; Keynotes: Should Note 2 indicate "To Be Removed"? Please verify.
4. Sheet S4.1; Keynotes: Should Note 1 indicate "To Be Removed"? Please verify.
5. Sheet S5.1; Keynotes: Should Note 4 indicate "To Remain"? Please verify.
6. Sheet S6.1; Detail 8: In the 20" square pier, please indicate a spacing on the #3 ties, or give a quantity.
7. General: Please provide a project valuation (labor + materials).
8. General: Please provide a Special Inspection Certificate with Parts A and B complete.
9. General: Please provide written responses to all review comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/01/2020 SMONTES1 APPROVAL SHELF Completed
10/01/2020 SMONTES1 OUT TO CUSTOMER Completed
10/01/2020 SMONTES1 REJECT SHELF Completed