Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T20CM03737
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/13/2020 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 09/29/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Completed | 1. Sheet X1; Code Review Summary: Please revise the ICC/ANSI Edition to 2009. 2. Sheet X1; Code Review Summary: Please revise the Building Classification to R-2 for multi-family housing. 3. Sheet S2.1; Keynotes: Should Note 2 indicate "To Be Removed"? Please verify. 4. Sheet S4.1; Keynotes: Should Note 1 indicate "To Be Removed"? Please verify. 5. Sheet S5.1; Keynotes: Should Note 4 indicate "To Remain"? Please verify. 6. Sheet S6.1; Detail 8: In the 20" square pier, please indicate a spacing on the #3 ties, or give a quantity. 7. General: Please provide a project valuation (labor + materials). 8. General: Please provide a Special Inspection Certificate with Parts A and B complete. 9. General: Please provide written responses to all review comments. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/01/2020 | SMONTES1 | APPROVAL SHELF | Completed |
| 10/01/2020 | SMONTES1 | OUT TO CUSTOMER | Completed |
| 10/01/2020 | SMONTES1 | REJECT SHELF | Completed |