Permit Number: T20CM03730
Parcel: 11706067A

Review Status: Active

Review Details: WALK THRU - COMM

Permit Number - T20CM03730
Review Name: WALK THRU - COMM
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
06/17/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

1. Show all electrical equipment locations including sub panels on the site plan.
2. Two services not allowed on a building without special permission from the Building official. See NEC 230.2. You may apply or appeal to the building official for a code variance.
3. The Panel identifications do not correlate between the line diagrams and the panel schedules. Please clarify.
4. Provide complete panel schedules that include load calcs.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
07/13/2020 STEVE SHIELDS ZONING REVIEW Passed