Review Details: WALK THRU - COMM
Permit Number - T20CM03730
Review Name: WALK THRU - COMM
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/17/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Show all electrical equipment locations including sub panels on the site plan. 2. Two services not allowed on a building without special permission from the Building official. See NEC 230.2. You may apply or appeal to the building official for a code variance. 3. The Panel identifications do not correlate between the line diagrams and the panel schedules. Please clarify. 4. Provide complete panel schedules that include load calcs. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |