Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM03684
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/01/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comment; Sheet A3; Exit Access Travel Distance: Per the IBC Section 1017.3, the exit access travel distance shall be measured along the natural and unobstructed path along horizontal and vertical egress travel to the exit. This sheet indicates portions of the exit access travel distances measured along diagonal paths. It appears the maximum allowable exit access travel distance of 75' will be exceeded for one exit (IBC Table 1006.2.1). Please verify. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/07/2020 | PC_TGUTHEI1 | REJECT SHELF | Passed |
| 09/07/2020 | PC_TGUTHEI1 | APPROVAL SHELF | Passed |
| 09/07/2020 | PC_TGUTHEI1 | OUT TO CUSTOMER | Completed |