Permit Number: T20CM03684
Parcel: 12217001A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM03684
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/21/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 2; Sheet A1 (Required Plumbing Fixtures): Section 2902.2 Exception 4 indicates separate facilities shall not be required in business occupancies with 25 or fewer occupants. This exception does not apply to a factory use. Please verify.
2. Previous Comment 5; Sheet A3 (Allowable Exit Access Travel Distance): Per the IBC Section 1017.3, the exit access travel distance to an exit shall be measured along the natural and unobstructed path of horizontal and vertical egress (not diagonal). Please revise that measurement on the Floor Plan.
3. General: Please provide written responses to all review comments.
08/21/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/31/2020 VLEON1 APPROVAL SHELF Completed
08/31/2020 VLEON1 OUT TO CUSTOMER Completed
08/31/2020 VLEON1 REJECT SHELF Completed