| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/11/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 08/21/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comment 2; Sheet A1 (Required Plumbing Fixtures): Section 2902.2 Exception 4 indicates separate facilities shall not be required in business occupancies with 25 or fewer occupants. This exception does not apply to a factory use. Please verify. 2. Previous Comment 5; Sheet A3 (Allowable Exit Access Travel Distance): Per the IBC Section 1017.3, the exit access travel distance to an exit shall be measured along the natural and unobstructed path of horizontal and vertical egress (not diagonal). Please revise that measurement on the Floor Plan. 3. General: Please provide written responses to all review comments. |
| 08/21/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |