Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM03630
Parcel: 13316024M

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM03630
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. The previous electrical plan review comments were not addressed on the second plan submittal as stated in the response letter.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements,
09/02/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/22/2020 ROBERT SHERRY WATER REVIEW Completed
09/22/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Show the new 3" floor cleanout downstream of S-2 on the waste & vent isometric. [Initial comment: Provide cleanouts for all horizontal drains (e.g. the 3" horizontal drain downstream of the clothes washer). Reference: Section 708.1.1, IPC 2018.]
2. The requirement of Section C404.5 is a maximum distance of 24" from the hot water source to the lavatory stop valve. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.]
09/22/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Correct the arithmetic used to calculate the required ventilation. The determination of the required ventilation for air handlers serving multiple zones requires the balancing data (supply CFM) for each zone and the calculations described in Sections 403.3.1.1.2.3.1 through 403.3.1.1.2.3.4, IMC 2018. Reference: Section 403.3.1.1.2.3, IMC 2018. [Initial comment: The City of Tucson has adopted the 2018 IMC as the approved method for calculating ventilation requirements.]
2. Condensate drains may not terminate over a roof drain or gutter unless the roof drain or gutter terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage. Only one of the four roof drains on the building terminates in a landscaped area. Show the routing of the condensate drains on the drawing. (Note: the north arrows on sheets M1.1 and P1.1 are incorrect.) [Initial comment: Condensate drains shall be terminated at an approved disposal location. Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson.]
3. Locating the backdraft damper in the duct as shown in the dryer duct exhaust detail will require the addition of an accessible cleanout for the backdraft damper. Reference: Section 504.3, IMC 2018. [Initial comment: Revise the design for the termination of the clothes dryer exhaust to include a backdraft damper. Reference: Section 504.4, IMC 2018.]