Permit Number: T20CM03629
Parcel: 11709123A

Address:
246 W 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM03629
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/23/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A0; Code Analysis: The Project Description indicates a new 1200 SF auto repair building that will be replacing a demolished building. This portion will be reviewed as a new building that must meet the requirements of the 2018 IBC.
2. Sheet A0; Code Analysis: The Occupancy Group is indicated as F-1 for Auto Repair. Please revise that classification to S-1 per the IBC Section 311.2.
3. Previous Comment 2: Please provide calculations on the drawings for the required plumbing fixtures for the total building occupant load.
4. Previous Comment 7; Sheet A2: The Typical Masonry Reinforcing Schedule still indicates #5 @ 32" o.c. typical reinforcing, which does not match the structural calculations. Please revise the schedule.
5. General: Please provide written responses to all review comments.
04/02/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL


PROJECT: Auto Rental and Sales LLC - 246 W 22nd St
T20CM03629 (DP20-0096)
Building Plan (2nd Review)

TRANSMITTAL DATE: April 2, 2021

1. Zoning has reviewed the building plans for compliance with the submitted development package DP20-0096. While the building plans are consistent with the submitted DP as it relates to the zoning review purview of the building footprint, building height, square footage, site conditions etc., zoning cannot approve the building plans until the DP is approved and all PDSD Commercial Plans reviewers have approved the building plans.

If you have any questions about this transmittal, please contact Elisa Hambllin at Elisa.Hamblin@tucsonaz.gov
04/02/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change See previous comment 2 - Show how roof drainage will not be directed onto the sidewalk. Plans need to show how this will be addressed to ensure no discharge onto the sidewalks.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov