Permit Number: T20CM03627
Parcel: 12006059D

Address:
3853 S 6TH AV

Review Status: Active

Review Details: OTHER

Permit Number - T20CM03627
Review Name: OTHER
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
06/19/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Replacement of AC units constitutes new work so the submittal will require documentation including a heating/cooling load calculation to justify the capacities of the units being installed (Sections C403.3,and C403.3.1, IECC 2018). Documentation will also be required to show that the units themselves comply with Sections C403.3.2, C403.4, and C403.5, IECC 2018 for efficiency, controls, and economizers. While ventilation calculations are not required, a test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous AC unit provided.
07/06/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Passed