Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM03606
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/25/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The new wall type (W6) has a combustible structure (i.e. wood studs) and does not comply with Section 507.2.6, IMC 2018. [Second comment: Comment not addressed by architect. Note that walls within 18-inches of the hood must comply with Section 507.2.6, IMC 2018 (e.g. portion of wall-type W3 adjacent to the hoods).] [Initial comment: Revise the W2 interior partition adjacent to the west end of the new hoods to comply with the requirements of Section 507.2.6, IMC 2018 (i.e. non-combustible structure, gypsum board, and stainless steel finish).] |
| 06/25/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed |