Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM03606
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/23/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/23/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Comment not addressed by architect. Note that walls within 18-inches of the hood must comply with Section 507.2.6, IMC 2018 (e.g. portion of wall-type W3 adjacent to the hoods). [Initial comment: Revise the W2 interior partition adjacent to the west end of the new hoods to comply with the requirements of Section 507.2.6, IMC 2018 (i.e. non-combustible structure, gypsum board, and stainless steel finish).] |
| 06/23/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | There are now two 120-degree hot water lines in detail 1/P2.1; label the hot water line that by-passes the temperature mixing valve as 140-degree hot water. [Initial comment: Relabel the 140-degree hot water and 120-degree hot water lines in detail 1/P2.1; they are reversed.] |
| 06/25/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Completed |