Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM03606
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/15/2020 | SAMUEL ROGERS | ZONING | REVIEW | Approved | |
| 06/15/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the W2 interior partition adjacent to the west end of the new hoods to comply with the requirements of Section 507.2.6, IMC 2018 (i.e. non-combustible structure, gypsum board, and stainless steel finish). 2. Verify that the construction of the existing wall north of the new hoods complies with the requirements of Section 507.2.6, IMC 2018. |
| 06/15/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. The current adopted IECC is the 2018. Please revise the lighting calcs utilizing the 2018 IECC Code. 2. Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the new exterior luminaires. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |
| 06/15/2020 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed | |
| 06/15/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1.0; Floor Plan: The exit access travel distances at all 3 exits indicates 75' as the maximum. Per the IBC Table 1017.2, an A-2 Occupancy Classification with no sprinkler system has a maximum allowable travel distance of 200'. Please revise that number at all exits. 2. Sheet A.1; Floor Plan: The measurement of the exit access travel distance must follow the IBC Section 1017.3. The travel distance must be measured along horizontal and vertical paths (no diagonals). Please revise the plan, and indicate the new travel distances. 3. Sheet A1.0; Partition Types: In the W3 description, it indicates "attach to existing masonry wall". Please indicate in that description how to attach the new studs to the existing masonry wall. 4. General: Please provide written responses to all review comments. |
| 06/15/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/15/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. The Symmons thermostatic mixing valve is listed to ASSE 1017, not ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018. 2. Relabel the 140 degree hot water and 120 degree hot water lines in detail 1/P2.1; they are reversed. 3. Show the cold water piping serving the K-5 hand sinks (as called for in the Replaced Kitchen Fixture Schedule). 4. Appliances (e.g. beverage dispensers, ice makers, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.14.1, IPC 2018 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2018. |
| 06/15/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/16/2020 | JVINCEN1 | FIRE | REVIEW | Approved |