Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM03594
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/02/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/08/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide the Envelope and Mechanical COMcheck Compliance Certificates and the Systems Design Report. [Third comment: The Table of Contents on sheet AS-100 shows a Mechanical COMcheck and a Systems Design Report as attachments but they have not been submitted. In addition, nothing has been submitted to verify that alterations to the building envelope comply with the current energy code (e.g. COMcheck Envelope Compliance Certificate).] [Second comment: Comment not addressed.] [Initial comment: Demonstrate energy code compliance for the alterations to the building envelope using calculations based on the current code. Reference: Sections C103.2, C303, C503.1, and C503.3, International Energy Conservation Code 2018.] |
| 03/08/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed |