Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T20CM03594
Parcel: 12406132A

Address:
1050 E 8TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM03594
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2020 JPEELDA1 FIRE REVIEW Reqs Change IEBC 2018 and what levelType of constructionIs the building sprinkleredType of occupancy and your occupant loads
06/18/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference: Section 107.2.1, IBC 2018.
2. Provide specifications for the proposed plumbing fixtures. Reference: Sections 303.4 and 402, IPC 2018.
06/18/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Demonstrate energy code compliance for the alterations to the building envelope using calculations based on the current code. Reference: Sections C103.2, C303, C503.1, and C503.3, International Energy Conservation Code 2018.
2. Provide construction documents drawn to scale and with sufficient detail and clarity to demonstrate that any proposed mechanical work complies with the applicable codes. Reference: Section 107.2.1, IBC 2018.
06/18/2020 ROBERT SHERRY WATER REVIEW Completed
06/25/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/25/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet AS-100: Please indicate all relevant codes on this sheet along with new material strengths (wood, masonry, concrete, reinforcing, steel, etc.).
2. Sheet A-101: Please provide a Code Analysis on this sheet for the Leasing Center (some is already included in the General Notes). Include the Occupancy Classification, Construction Type, Square Footage, Occupant Load, Sprinklers/No Sprinklers, and Exit Requirements (number of exits and exit width). Indicate there is no new work on the second floor.
3. Sheet A-101; General Notes (Note 3): This note indicates MEP trades will be design build. All design and drawings for these reviewers will be required on the permit drawings.
4. Sheet A-101; Keynotes: Please indicate in a note that not all Keynotes are includedon the plans and elevations on this sheet.
5. Sheet A-101; Keynotes: Keynote 21 references a drink rail at 42" above finish floor. Per the 2009 ICC/ANSI Section 902.4, this height must be between 28" and 34" above finish floor. Please revise.
6. Sheet A-101; First Floor Plan: Keynote 14 references a bottle filling station at accessible height. Please indicate a spout height of 36" maximum above finish floor per ICC/ANSI Section 602.4.
7. Sheet A-101; First Floor Plan: Keynote 13 references a bench mounting height at accessible height. Please indicate a bench height between 17" and 19" above finish floor per ICC/ANSI Section 903.5.
8. Sheet A-101; First Floor Plan: Keynote 11 references an accessible height toilet. Please indicate a seat height between 17" and 19" above finish floor per ICC/ANSI Figure 604.4.
9. Sheet A-101; First Floor Plan: Keynote 12 references accessible shower, grab bars, seats, and hand showers. Please add this information on Elevations per ICC/ANSI Section 608.
10. Sheet A-101; First Floor Plan: Please add Keynotes to this plan at all new interior walls.
11. Sheet A-101: Please indicate restroom grab bars by adding ICC/ANSI Figures 604.5.1 and 604.5.2 on this sheet.
12. General: Please provide a valuation (labor + materials) for this project.
13. General: Please provide written responses to all review comments.
07/02/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
Please provide complete electrical power and lighting plans. See City of Tucson Electrical Commercial Plan Submittal Requirements can be downloaded at www.tucsonaz.gov/pdsd; Permit Review; Commercial Permits; Commercial Plan Review.
Ref; IBC sec. 107.2.1
R4-30-302. Electrical Plans
1. A registrant shall prepare and submit drawings and specifications for a new electrical system or an addition or modification to an existing electrical system provided the service and associated electrical feeders exceeds 600 amperes 120/240 volts, single phase or 225 amperes 120/208 volts, three phase and the fault current exceeds 10,000 amperes.
2. In all cases a registrant shall design:
a. Electrical installations in hospitals or other buildings with surgical operating rooms regulated by Article 517 of the National Electrical code (1990 edition) incorporated herein by reference and on file with the Office of the Secretary of State.
b. Electrical installations in locations classified as hazardous in Article 500 of the National Electrical Code (1990 edition) incorporated herein by reference and on file with the Office of the Secretary of State.
c. Electrical installations in locations classified as hazardous in Article 500 of the National Electrical Code (1990 edition) with the exception of gasoline dispensing or repair garages.
d. A registrant shall design an alarm or signaling system that is required for life safety or code compliance.

Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code.
07/06/2020 LOREN MAKUS ENGINEERING REVIEW Reqs Change A floodplain use permit is required. Complete and submit floodplain use permit application.
07/07/2020 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: Wildcat Leasing and Fitness Remodel
T20CM03594 (1st Review)
1050 E 8th Ave

TRANSMITTAL DATE: July 7, 2020

1. Zoning has reviewed the building plans but until DP19-0261 has been approved Zoning cannot approve the building plans. Also unit all other PDSD Commercial Plans reviewers have approved the building plans Zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956