Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T20CM03579
Parcel: 126041360

Address:
1002 N JERRIE AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM03579
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/25/2020 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size and serial number of the water meter serving this building along with the total water demand it supplies. Reference: Section 107.2.1, IBC 2018.
06/25/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide guards for equipment located within 10 feet of a roof edge or of a walking surface that is elevated more than 30 inches above the adjoining grade. Reference: Section 304.11, IMC 2018.
2. Provide ventilation calculations for the apartments. Reference: Section 403.3.2, IMC 2018.
3 Provide complete specifications for EF-1. Based on the description in the mechanical specifications it appears to be a ceiling-mounted kitchen hood exhaust but detail 5/M2.0 depicts it as a roof-mounted exhaust fan. Reference: Section 107.2.1, IBC 2018.
07/16/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Correct the arithmetic in the 2-bedroom fixture calculations (5x12=60, not 25). Reference: Section 107.2.1, IBC 2018.
2. Clarify the appliance tags (e.g. is P1 a clothes washer or is it a kitchen sink?). Reference: Section 107.2.1, IBC 2018.
3. Detail 1/P3.0 calls for the T&P relief to terminate into a mop basin below the water heater; where is the mop basin? Reference: Section 107.2.1, IBC 2018.
4. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves. Reference: Section 604.9, IPC 2018.
07/30/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/31/2020 VLEON1 APPROVAL SHELF Completed
07/31/2020 VLEON1 OUT TO CUSTOMER Completed
07/31/2020 VLEON1 REJECT SHELF Completed