Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/10/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet S.1; Detail 1: Please provide the pier diameter on the detail. 2. Sheet S.1 (General Structural Notes); Structural Calculations (Page D2): The calculations indicate an allowable soil bearing value of 1000 psf, while the General Structural Notes indicate 1500 psf. Please coordinate. 3. General: Please provide a site plan with dimensions from the new structure to property lines, other structures, etc. 4. General: Please provide a Special Inspection Certificate with Parts A and B completed. This form may be found at www.tucsonaz.gov/PDSD. |
06/10/2020 | SAMUEL ROGERS | ZONING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/14/2020 | ARUIZ1 | OUT TO CUSTOMER | Completed |