Permit Number: T20CM03507
Parcel: 13502032A

Address:
6620 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T20CM03507
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2020 JPEELDA1 FIRE REVIEW Approved
06/23/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S4.0; Plan View: The IBC Table 602 indicates for a IIB Construction Type structure with a U Occupancy Classification, a fire separation distance of at least 10' is required to an imaginary property line (Section 705.3). The Building Official allows the fabric structures to be a minimum fire separation of 10' from existing buildings (this would be 5' from the imaginary property line). The location of this structure does not meet that criteria. Please revise.
06/24/2020 AHINES2 ENGINEERING REVIEW Passed
06/24/2020 ALEXANDRA HINES ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/31/2020 ARUIZ1 OUT TO CUSTOMER Completed