Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM03500
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/09/2020 | ELISA HAMBLIN | ZONING | REVIEW | Approved | |
| 06/09/2020 | EHAMBLI1 | ENGINEERING | REVIEW | Passed | |
| 06/10/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide a panel schedule for Panel 'L1'. 2018 IBC sec 107.2.1, 2017 NEC. |
| 06/10/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 06/10/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/11/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | While the primary occupancy of the suite has not changed from office, the meeting room has a different use and therefore requires an analysis of the ventilation requirements. Provide ventilation calculations to verify that the meeting room has sufficient ventilation. Reference: Section 403.3.1.1, IMC 2018. |
| 06/11/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/11/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 06/12/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |