Permit Number: T20CM03500
Parcel: 128100540

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM03500
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2020 ELISA HAMBLIN ZONING REVIEW Approved
06/09/2020 EHAMBLI1 ENGINEERING REVIEW Passed
06/10/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide a panel schedule for Panel 'L1'.
2018 IBC sec 107.2.1, 2017 NEC.
06/10/2020 JPEELDA1 FIRE REVIEW Approved
06/10/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/11/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change While the primary occupancy of the suite has not changed from office, the meeting room has a different use and therefore requires an analysis of the ventilation requirements. Provide ventilation calculations to verify that the meeting room has sufficient ventilation. Reference: Section 403.3.1.1, IMC 2018.
06/11/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/11/2020 ROBERT SHERRY WATER REVIEW Completed
06/12/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved