Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM03485
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/24/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 07/02/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | If the showers do not have prefabricated receptors, provide details to show that the receptor construction complies with the requirements of Section 421.5, IPC 2018. |
| 07/02/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/02/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the design of the dryer exhaust system. The mechanical ceiling plan calls out the vent termination as EF-2; coordinate detail 101 with the dryer fan schedule. Reference: Section 107.2.1, IBC 2018. 2. Show that the exhaust flow rate for each of the four new restrooms complies with the requirements of Table 403.3.1.1, IMC 2018 |
| 07/06/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/14/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet TS1; Code Study (Plumbing Fixtures): This section indicates 2 existing water closets and 2 existing lavatories. Please add verbiage indicating 1 new women's water closet and lavatory, and 1 new men's water closet and lavatory have been added. 2. Sheet D1; Plans: Please provide a north arrow on the Key Plan and the Demolition Floor Plan. 3. Sheet D1; Demolition Floor Plan: There are several locations where a dashed wall (existing construction to be removed) is referenced by a Key Note D6.1 (existing interior wall to remain). Please coordinate. 4. Sheet D1; Demolition Floor Plan: There are a few locations where a dashed counter top and cabinetry (existing construction to be removed) is referenced by a Key Note D6.5 (existing cabinetry and counter top to remain). Please coordinate. 5. Sheet D1.1; Plans: Please provide a north arrow on the Key Plan and the Reflected Ceiling Plan. 6. Sheet A1; Plans: Please provide a north arrow on the Key Plan and the Floor Plan. 7. Sheet A2; Plans: Please provide a north arrow on the Key Plan and the Reflected Ceiling Plan. 8. Sheet A2; Relfected Ceiling Plan: Please indicate the exit lights on the Reflected Ceiling Plan. 9. General: Please provide an Egress Plan for this project, indicating allowable and actual exit access travel distances per the IBC Section 1017. 10. General: Please provide written responses to all review comments. |