Permit Number: T20CM03408
Parcel: 117110170

Address:
177 N CHURCH AV

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T20CM03408
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show that the proposed cooling tower meets the minimum efficiency requirements of Table C403.3.2 (8), IECC 2018.
06/04/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/08/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/11/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S2.0; Chiller Platform Framing: Please provide structural calculations for the support platform design.
2. General: Please provide a Special Inspection Certificate with Parts A and B completed.