Permit Number: T20CM03386
Parcel: 12701003W

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM03386
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/04/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/04/2020 JOHN VAN WINKLE ENGINEERING REVIEW Passed
06/04/2020 ROBERT SHERRY WATER REVIEW Completed
06/04/2020 JPEELDA1 FIRE REVIEW Approved
06/05/2020 SAMUEL ROGERS ZONING REVIEW Approved
06/05/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A-1 (Floor Plan Keyed Note 9); Sheet A-3 (Detail 6): The detail indicates a one hour wall, while Note 9 indicates a two hour wall. Please coordinate.
2. Sheet A-3; Detail 6: Please provide a U.L. Listing Number for the shaft wall assembly.
3. General: Please provide written responses to all review comments.
06/05/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/16/2020 ARUIZ1 ELECTRICAL-COMMERCIAL REVIEW Needs Review