Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T20CM03369
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/29/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide detailed information about the proposed work. Such as: (a) Amp, AIC rating of the equipment. (b) Is this a like for like replacement? (c) Are you installing new sub-panels or are they existing to remain? (d) Is this Service going to be installed in the same location? If not provide a site plan showing the new location on the premises. (e) If this is an increase in load or amp rating, provide a complete line diagram. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/27/2020 | ARUIZ1 | OUT TO CUSTOMER | Completed |