Permit Number: T20CM03355
Parcel: 125041800

Address:
2404 E 1ST ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM03355
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2020 ANDREW CONNOR NPPO REVIEW Passed
06/03/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM03355
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.

GENERAL COMMENTS:

1. Limit all code references to those recognized by the City of Tucson. Adopted 2018 codes are listed at the Planning & Development Services web site. Update the code references used for the design shown on page #3 & 5.

SITE PLAN:

1. Indicate the location of buildings with setback dimensions and of the electrical panel, R106.1.1.

FLOOR PLANS:

1. Provide a floor plan (scale ¼” = 1’) of the proposed room and adjacent room providing entrance into the proposed space, R106.1.1. It is unclear if this space is a room expansion or separate room.

STRUCTURAL PLANS:

1. Provide a complete roof framing plan with a supported beam sized with appropriate load carrying capacity, R301.1. A clay tile roof covering adds an additional 10 #/FT dead load. Also, a beam must include a post support with connection to a foundation. Perhaps a roof truss system should be considered.
2. Provide a header schedule and show opening sizes supporting new roof consistent with Table 502.5(1) & R602.7(1).

SECTIONS - DETAILS:

1. Update the cross-section detail of the new exterior wall showing exterior wood sheathing and wall framing with a 6” clearance above the ground (R317.1 item 5) and with minimum ½” diameter anchor bolt, R602.10.8 & R403.1.6. extending into a foundation with a minimum 12” depth.
2. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806.
3. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.
4. A vented attic space requires a calculation for showing the attic ventilation opening size using 1 to 150 of attic area in compliance with R806.2. Provide appropriate upper and lower space vents when applying the reduced area calculation. Account for the existing attic space if removing or blocking existing vents.

MECHANICAL PLANS:

1. Provide heating facilities in all habitable rooms, R303.9. Also, shown any cooling system.

ELECTRICAL PLANS:

1. Smoke alarms are required outside each separate sleeping area, R314.3.2. Show a smoke alarm in each bedroom and outside in the immediate vicinity.
2. Show receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet, E3901.2. .
3. Protection of all interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors requires combination type arc-fault circuit interrupters, E3902.16.
4. Provide notation requiring tamper resistant receptacles for 125 volt, 15A and 20A receptacles, R4002.14.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
06/29/2020 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: T20CM03355
2404 E 1st St.
Bedroom Addition
Residential (1st Review)

TRANSMITTAL DATE: June 29, 2020

The room addition plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

1. Provide a side street perimeter yard setback dimension. The minimum setback to a side street property line is ten (10) feet (UDC Section 6.4.5.C.1.b) to Norton Ave.

2. The 15' front street perimeter yard setback does not meet the minimum requirement. The minimum setback to the front street perimeter property line is the greater of twenty (20) feet, or one and one-half (1 ½) the height of the proposed wall ((UDC 6.4.5.C.1.a). A Design Development Options (DDO) will be required to be submitted and approved prior to these building plans. DDO requirements can be found at https://www.tucsonaz.gov/files/pdsd/2019_DDO_for_Setback_and_Height_UDC.pdf

3. The plot plan shall be drawn at an engineering scale, i.e. 1" = 10' or 1" = 20'.

4. Provide a lot coverage calculation on the plan.

5. Show the locations of all utilities on the plan.

6. Provide a dimension from the center of 1st Street to the curb and from the curb to the street property line along 1st. The distance from center of 1st to the curb should be 20' and from the curb to property line is 10'

7. Provide a dimension from the center of Norton Avenue to the curb and from the curb to the street property line along Norton. The distance from center of Norton to the curb should be 15' and from the curb to property line is 10'

8. Indicate he zoning of the property and of the surrounding properties.

9. Provide a legal description on the plan. This description should be "SPEEDWAY HEIGHTS LOT 8 BLK 12".
10. Provide a full floor plan of the existing house so that the number of bedrooms can be verified.

11. Based on the most current aerial photos there appears to be some type of structure in the rear yard. Show this structure on the plan and include it in the lot coverage calculation.

Residential plot plan requirements can be found at https://www.tucsonaz.gov/pdsd/all-application-forms-submittal-requirements.
07/01/2020 LOREN MAKUS ENGINEERING REVIEW Passed