Permit Review Detail
Review Status: Active
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/WWM
Permit Number - T20CM03327
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/WWM
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/08/2020 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Section Manager PROJECT: T20CM03327 5517 S 13th Ave Gazebo w/storage Residential (1st Review) TRANSMITTAL DATE: June 8, 2020 The room addition plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 1. Provide the drawing pdf's as a single pdf file. 2. 3. Provide documentation that the shed shown in the northeast corner of the site has been permitted. 4. Provide a plot plan that meets the requires as shown at the following web page: Residential plot plan requirements can be found at https://www.tucsonaz.gov/pdsd/all-application-forms-submittal-requirements. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 06/11/2020 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | PROVIDE A COMPLETE PLAN SET IN A SINGLE FILE SHOWING BEAM AND RAFTER SIZES AND FOUNDATION SIZE WITH FASTENERS. |
| 06/18/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Passed |